| Test & Sequence
|
| Bending Test |
Die.20 (D+d) ± 5%; 3-cycles |
| Partial Discharge Test |
1.5 U0Q< 5PC |
| Tan Delta, at Elevated temp. |
U0tC= 90º C - 50ºC,
+10ºC |
| Heat Cycle |
2 U0; 20 load cycles |
| Voltage Test |
8/16 Hr. TC= 95ºC 5ºC, +10ºC
(No Breakdown) |
| Partial Discharge Test |
1.5 U0; Q<5PC |
| Impulse Voltage with stand test |
325 kV |
| High Voltage (a.c) Test |
2.5 U0 (15 min) |
| High Voltage (a.c) special Test |
3 U0 (4 Hrs) |
| Water Penetration Test |
31.10 cycles 8/16 tC = 90ºC +5ºC
90ºC, -5ºC, +5ºC 1m.
Head of Water |