| Home > Products > XLPE
Cables > High Voltage: 66 kV XLPE Cables > Basic Design >
Lead Sheath Construction |
| Lead Sheath Construction |
|

|
Reference :
1. Copper Conductor
2. Extruded Semi conducting XLPE
3. XLPE Insulation
4. Semi-Conducting XLPE
5. Semi-Conducting Water Swellables Tape
6. Extruded Seamless Lead Alloy 'E' Sheath
7. Semi conducing Bedding Tape
8. Copper Wire Screen
9. Counter helix Copper Tape
10. Extruded Black PVC with a Graphite Coat |
|
|
| Conductor:
The conductor consists of annealed copper wires compacted having
a smooth circular shape for sizes upto 1000mm2 cross-sectional
area conforming to IEC:228 or IS :8130-84.
Note: In special cases, Aluminium Conductors are
provided depending on specific need of the customer.
Beyond 1000mm2 Milliken Conductors (segmental) are recommended.
Conductor Screen: The conductor screen consists
of a layer of smooth black extruded semi-conducting XLPE compound
firmly bonded with the insulation. This eliminates electrical discharges
at the interface between conductor and insulation.
Insulation:
The insulation consists of super clean XLPE compound.
The extrusion process is conducted in clinically clean environment.
The insulation thickness conforms to IS: 7098 (part 3) or as per customer's
specification.
Insulation Screen: The screen consists of smooth
black semi-conducting XLPE compound firmly bonded with a smooth
interface with the insulation. The conductor screen, insulation
and insulation screen and extruded simultaneously in Dry-Cure Process
Moisture Barrier: To make the cable longitudinally
watertight a semi-conducting water blocking tape is applied over
the core, to prevent water penetration in the cable. The tape is
of non-woven material which has non-biodegradable characteristics.
Seamless Lead Sheath: Extruded Seamless Lead Alloy
'E' Sheath having high fatigue endurance limit is provided. This
is the most popular metallic sheath used worldwide.
Features:
- Hermetically seales-Corrosion resistant
- Mechanical protection
- Serves as an earthed metallic screen- To carry earth fault current
- Low sheath losses and higher current rating
Copper Wire Screen: Copper Wires are applied
over the Lead Sheath to carry the necessary earth fault current
alongside the Lead Sheath. This is particularly applicable where
the requirement of earth fault current is high. This also helps
in reducing the weight of the cable by avoiding excess lead thickness.
A counter open helix copper tape is provided over the copper wires.
Note: Semi-conducting tape(s) is generally provided
between the Lead and Copper Screen.
Jacketing: The jacket material consists of Extruded
Black PVC (ST2) or High Density Polyethylene (HDE). A graphite coat
is provided over the outer surface of the sheath. |