Nicco Brand PVC Power and Control Cables are manufactured conforming to IIS: 1554 and the details are given below:

Conductor : The construction of the conductors shall be as follows :

Nominal Cross-Sectional Area Solid / Standard Flexibility Class
Copper mrn2 Aluminium mm2

1.5

2.5 to 6

10 and above

1.5

2.5 to 10

16 and above

Solid

Solid/Standard

Standard

Class I (Table-1) of IS:8130*

Class 1 (Table- 1) of IS : 3150*

Class2 (Table-2)  of lS: 8l30*

[ * Specification for conductors for Insulated electric cables and flexible cords.]

Conductors of nominal area less than 16 mm2 shall be circular only- Conductors of nominal area and above may be circular or shaped.

Cables with reduced neutral conductor shall comply with the Main Power conductor combination given in the following table :

Nominal Cross-Sectional Area of
Main Power Conductor mm2
Cross-Sectional Area of
Reduced Neutral Conductor mm
2
25 16
35 16
50 25
70 35
95 50
120 70
150 70
185 95
240 120
300 150
40O 185
500 240
630 300

 